Cut Sheet
Table Of Contents
- 1. Intended Use
- 2. Installation Instructions
- 3. AC-Input
- 4. DC-Input
- 5. Input Inrush Current
- 6. Output
- 7. Hold-up Time
- 8. DC-OK Relay Contact
- 9. Efficiency and Power Losses
- 10. Functional Diagram
- 11. Front Side and User Elements
- 12. Connection Terminals
- 13. Lifetime Expectancy
- 14. MTBF
- 15. EMC
- 16. Environment
- 17. Safety and Protection Features
- 18. Dielectric Strength
- 19. Approved, Fulfilled or Tested Standards
- 20. Regulatory Product Compliance
- 21. Physical Dimensions and Weight
- 22. Accessories
- 22.1. ZM10.WALL - Wall/Panel Mount Bracket
- 22.2. YR20.242 - Redundancy Module
- 23. Application Notes
- 23.1. Peak Current Capability
- 23.2. Charging of Batteries
- 23.3. Series Operation
- 23.4. Parallel Use to Increase Output Power
- 23.5. Parallel Use for Redundancy
- 23.6. Operation on Two Phases
- 23.7. Use in a Tightly Sealed Enclosure
- 23.8. Mounting Orientations
CP5.121
CP
-Series
12V, 10A, 120W, SINGLE PHASE INPUT
Aug 2021 / Rev. 1.2 DS-CP5.121-EN All values are typical figures specified at 230Vac, 50Hz input voltage, 12V 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
17/28
17. S
AFETY AND
P
ROTECTION
F
EATURES
Isolation resistance
Min. 500MOhm
At delivered condition between input and output,
measured with 500Vdc
Min. 500MOhm
At delivered condition between input and PE,
measured with 500Vdc
Min. 500MOhm
At delivered condition between output and PE,
measured with 500Vdc
Min. 500MOhm
At delivered condition between output and DC-OK
contacts, measured with 500Vdc
PE resistance
Max. 0.1Ohm
Resistance between PE terminal and the housing in
the area of the DIN rail mounting bracket.
Output o
ver-voltage protection Typ. 16.2Vdc
Max. 17Vdc
In case of an internal defect, a redundant circuit limits the maximum output
voltage. The output shuts down and performs three restart attempts. If the
failure continues, the output shuts down. Cycle input power to reset.
Class of protection
I According to IEC 61140
A PE (Protective Earth) connection is required
Degree of
protection IP 20 According to EN/IEC 60529
Over
-temperature protection Included
Output shut-down with automatic restart.
Temperature sensors are installed on critical
components inside the unit and turn the unit off in
safety critical situations, which can happen e.g.
when ambient temperature is too high, ventilation
is obstructed or the derating requirements are not
followed. There is no correlation between the
operating temperature and turn-off temperature
since this is dependent on input voltage, load and
installation methods.
Input transient protection
MOV (Metal Oxide
Varistor)
For protection values see chapter 15 (EMC).
Internal input fuse
Included
Not user replaceable slow-blow high-braking
capacity fuse
Touch current
(leakage current) Typ. 0.10mA / 0.27mA At 100Vac, 50Hz, TN-,TT-mains / IT-mains
Typ. 0.13mA / 0.38mA At 120Vac, 60Hz, TN-,TT-mains / IT-mains
Typ. 0.20mA / 0.60mA At 230Vac, 50Hz, TN-,TT-mains / IT-mains
Max. 0.13mA / 0.35mA At 110Vac, 50Hz, TN-,TT-mains / IT-mains
Max. 0.17mA / 0.51mA At 132Vac, 60Hz, TN-,TT-mains / IT-mains
Max. 0.27mA / 0.81mA At 264Vac, 50Hz, TN-,TT-mains / IT-mains