Cut Sheet
Table Of Contents
- 1. Intended Use
- 2. Installation Instructions
- 3. AC-Input
- 4. DC-Input
- 5. Input Inrush Current
- 6. Output
- 7. Hold-up Time
- 8. DC-OK Relay Contact
- 9. Efficiency and Power Losses
- 10. Functional Diagram
- 11. Front Side and User Elements
- 12. Connection Terminals
- 13. Lifetime Expectancy
- 14. MTBF
- 15. EMC
- 16. Environment
- 17. Safety and Protection Features
- 18. Dielectric Strength
- 19. Approved, Fulfilled or Tested Standards
- 20. Regulatory Product Compliance
- 21. Physical Dimensions and Weight
- 22. Accessories
- 22.1. ZM10.WALL - Wall/Panel Mount Bracket
- 22.2. YR20.242 - Redundancy Module
- 23. Application Notes
- 23.1. Peak Current Capability
- 23.2. Charging of Batteries
- 23.3. Series Operation
- 23.4. Parallel Use to Increase Output Power
- 23.5. Parallel Use for Redundancy
- 23.6. Operation on Two Phases
- 23.7. Use in a Tightly Sealed Enclosure
- 23.8. Mounting Orientations
CP5.121
CP
-Series
12V, 10A, 120W, SINGLE PHASE INPUT
Aug 2021 / Rev. 1.2 DS-CP5.121-EN All values are typical figures specified at 230Vac, 50Hz input voltage, 12V 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
16/28
16. E
NVIRONMENT
Operational temperature
-25°C to +70°C (-13°F to 158°F)
Operational temperature is the same as the
ambient or surrounding temperature and is
defined as the air temperature 2cm below the unit.
Storage temperature
-40°C to +85°C (-40°F to 185°F) For storage and transportation
Output de
rating
1.6W/°C
3W/°C
0.67A/1000m or 5°C/1000m
Between +45°C and +60°C (113°F to 140°F)
Between +60°C and +70°C (140°F to 158°F)
For altitudes >2000m (6560ft), see Fig. 16-2
The derating is not hardware controlled. The user has to take care by himself to stay below
the derated current limits in order not to overload the unit.
Humidity
5 to 95% r.h. According to IEC 60068-2-30
Atmospheric pressure
110-54kPa See Fig. 16-2 for details
Altitude
Up to 5000m (16 400ft) See Fig. 16-2 for details
Over
-voltage category III
According to IEC 60664-1 for altitudes up to
2000m
II
According to IEC 60664-1, for altitudes above
2000m
Degree of pollution
2 According to IEC 62477-1, not conductive
Vibration sinusoidal
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
According to IEC 60068-2-6
Shock
30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total
According to IEC 60068-2-27
Shock and vibration is tested in combination with DIN rails according to EN 60715 with a
height of 15mm and a thickness of 1.3mm and standard orientation.
Audible noise
Some audible noise may be emitted from the power supply during no load, overload or
short circuit.
Fig. 16-1 Output current vs. ambient temp. Fig. 16-2 Output current vs. altitude
Allowed Output Current at 12V
0
-25 0
45
70°C
7.5A
10A
12A
60
A
Ambient Temperature
A... 85 to 264Vac, continuous
B... short term
B
2000m
5000m
8A
10A
12A
Altitude
Allowed Output Current at 12V
B
A... Tamb < 60°C
B... Tamb < 45°C
C... Short term
A
C
AP
*)
80kPa
54kPa110kPa
0m
*) Atmospheric pressure