Cut Sheet
Table Of Contents
- 1. Intended Use
- 2. Installation Instructions
- 3. AC-Input
- 4. DC-Input
- 5. Input Inrush Current
- 6. Output
- 7. Hold-up Time
- 8. DC-OK Relay Contact
- 9. Efficiency and Power Losses
- 10. Functional Diagram
- 11. Front Side and User Elements
- 12. Connection Terminals
- 13. Lifetime Expectancy
- 14. MTBF
- 15. EMC
- 16. Environment
- 17. Safety and Protection Features
- 18. Dielectric Strength
- 19. Approved, Fulfilled or Tested Standards
- 20. Regulatory Product Compliance
- 21. Physical Dimensions and Weight
- 22. Accessories
- 22.1. ZM10.WALL - Wall/Panel Mount Bracket
- 22.2. YR20.242 - Redundancy Module
- 23. Application Notes
- 23.1. Peak Current Capability
- 23.2. Charging of Batteries
- 23.3. Series Operation
- 23.4. Parallel Use to Increase Output Power
- 23.5. Parallel Use for Redundancy
- 23.6. Operation on Two Phases
- 23.7. Use in a Tightly Sealed Enclosure
- 23.8. Mounting Orientations
CP5.121
CP
-Series
12V, 10A, 120W, SINGLE PHASE INPUT
Aug 2021 / Rev. 1.2 DS-CP5.121-EN All values are typical figures specified at 230Vac, 50Hz input voltage, 12V 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
15/28
15. EMC
The EMC behavior of the device is designed for applications in industrial environment as well as in residential,
commercial and light industry environments.
The device is investigated according to EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 61000-6-4.
EMC Immunity
Electrostatic discharge
EN 61000-4-2
Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field
EN 61000-4-3 80MHz-2.7GHz 20V/m Criterion A
Fast transients (Burst)
EN 61000-4-4
Input lines
Output lines
DC-OK signal (coupling clamp)
4kV
2kV
2kV
Criterion A
Criterion A
Criterion A
Surge voltage on input
EN 61000-4-5
L N
L
PE, N
PE
2kV
4kV
Criterion A
Criterion A
Surge voltage on output
EN 61000-4-5
+ -
+ / - PE
1kV
2kV
Criterion A
Criterion A
Surge voltage on DC
-OK EN 61000-4-5 DC-OK signal PE 1kV Criterion A
Conducted disturbance
EN 61000-4-6 0.15-80MHz 20V Criterion A
Mains voltage dips
EN 61000-4-11
0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
40% of 200Vac
70% of 200Vac
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms <8A
80Vac, 200ms >8A
140Vac, 500ms
Criterion A
Criterion C
Criterion A
Criterion A
Criterion A
Criterion C
Criterion A
Voltage interruptions
EN 61000-4-11 0% of 200Vac (=0V) 5000ms Criterion C
Powerful transients
VDE 0160 Over entire load range 750V, 0.3ms Criterion A
Performance criterions:
A: The device shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. The device may shut-down and restarts by itself. No damage or hazards for the device will occur.
EMC Emission
Conducted emission
input lines
EN 55011, EN 55032, FCC Part 15, CISPR 11, CISPR 32 Class B
C
onducted emission
output lines
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
Limits for local DC power
networks fulfilled
Radiated emission
EN 55011, EN 55032 Class B
Harmonic input current
(PFC) EN 61000-3-2 Fulfilled for Class A equipment
Voltage fl
uctuations, flicker EN 61000-3-3
Fulfilled
,
tested with constant
current loads, non pulsing
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and
(2) this
d
evice must accept any interference received, including interference that may cause undesired operation.
Switching Frequencies
PFC converter
30kHz to 140kHz Input voltage and output power dependent
Main converter
60kHz to 140kHz Output load dependent
Au
xiliary converter 30kHz to 60kHz Output load dependent