Cut Sheet

CP5.121
CP
-Series
12V, 10A, 120W, SINGLE PHASE INPUT
Aug 2021 / Rev. 1.2 DS-CP5.121-EN All values are typical figures specified at 230Vac, 50Hz input voltage, 12V 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
10/28
7. H
OLD
-
UP
T
IME
The hold-up time is the time during which a power supply’s output voltage remains within specification following the
loss of input power. The hold-up time is output load dependent. At no load, the hold-up time can be up to several
seconds. The green DC-OK LED is also on during this time.
AC 100V AC 120V AC 230V
Hold
-up Time Typ. 70ms 70ms 70ms At 12V, 5A, see Fig. 7-1
Min. 55ms 55ms 55ms At 12V, 5A, see Fig. 7-1
Typ. 35ms 35ms 35ms At 12V, 10A, see Fig. 7-1
Min. 27ms 27ms 27ms At 12V, 10A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
0
15
30
45
60
90ms
90
120 155 190
230Vac
Input Voltage
75
Hold-up Time
a
b
c
d
a) 12V 5A typ.
b) 12V 5A min.
c) 12V 10A typ.
d) 12V 10A min.
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
8. DC-OK
R
ELAY
C
ONTACT
This feature monitors the output voltage on the output terminals of a running power supply.
Contact closes
As soon as the output voltage reaches typ. 90% of the adjusted output voltage level.
Contact opens
As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 100ms. Dips shorter than 1ms will be ignored.
Switching hysteresis
Typically 0.4V
Contact ratings
Maximal 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load
Minimal permissible load: 1mA at 5Vdc
Isolation voltage
See dielectric strength table in chapter 18.
Fig. 8-1 DC-OK relay contact behavior
100ms
0.9* V
ADJ
<
1ms
10%
open
V
OUT
= V
ADJ
openclosed
closed
>
1ms