Datasheet
CP20.481
CP-Series
48V, 10A, SINGLE PHASE INPUT
P R E L I M I N A R Y
2) At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 2s. After this, the
output is switched off for approx. 18s before a new start attempt is automatically performed. This cycle is repeated as long as the overload
exists. If the overload has been cleared, the device will operate normally. See Fig. 6-3.
Fig. 6-1 Output voltage vs. output current,
typ.
Fig. 6-2 Output voltage in “parallel use”
mode, typ.
Output Voltage
(Single Use, typ.)
0
0 12.5
8
16
24
56V
32
40
48
20A7.52.5 5 10 15 17.5
Adjustment
Range
Output Current
A: continuous current
B: intermitted current
A
B
Output Voltage
(Parallel Use, typ.)
43V
048
45V
47V
49V
57V
51V
53V
55V
12A1062
Adjustment
Range
Factory
setting
Output Current
Fig. 6-3 Short-circuit on output, Hiccup
PLUS®
mode, typ. Fig. 6-4 Dynamic overcurrent capability, typ.
Output
Current
9/29
0
15A
18s
18s
18s
2s
2s
2s
t
Short -circuit
Normal
operation
Normal
operation
Output Voltage
(dynamic behavior, < 12ms)
0
8
16
24
56V
32
40
48
0
35A155202510 30
Adjustment
Range
Output Current
Sep. 2018 / Rev. 0.3 DS-CP20.481-EN All parameters are specified at 230Vac, 50Hz input voltage, 48V, 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany