Data Sheet

CP20.241, CP20.241-C1, CP20.241-S1,
CP20.241-S2, CP20.241-V1, CP20.242
CP-Series
24V, 20A, 480W, SINGLE PHASE
Sep. 2018 / Rev. 1.0 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
19. DIELECTRIC STRENGTH
The output voltage is floating and has no ohmic connection to the ground.
The output is insulated to the input by a double or reinforced insulation.
Type and routine tests are conducted by the manufacturer. Field tests may be conducted in the field using the
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all input-
terminals together as well as all output poles before conducting the test. When testing, set the cut-off current settings
to the value in the table below.
We recommend that either the + pole or the – pole shall be connected to the protective earth system. This helps to
avoid situations in which a load starts unexpectedly or can not be switched off when unnoticed earth faults occur.
Fig. 19-1 Dielectric strength
A B C D
Type test 60s 2500Vac 3000Vac 1000Vac 500Vac
Routine test 5s 2500Vac 2500Vac 500Vac 500Vac
Field test 5s 2000Vac 2000Vac 500Vac 500Vac
Cut-off current setting
for field test
> 10mA > 10mA > 20mA > 1mA
AD
C
B
B
*)
N
L
Input DC-ok
Earth, PE
Output
B
*)
When testing input to DC-OK ensure that the maximal voltage between DC-OK and the
output is not exceeded (column D). We recommend connecting DC-OK pins and the
output pins together when performing the test.
20/32
-
+