CP20.241, CP20.241-C1, CP20.241-S1,
CP20.241-S2, CP20.241-V1, CP20.242
CP-Series
24V, 20A, 480W, SINGLE PHASE
Sep. 2018 / Rev. 1.0 DS-CP20.241-EN - All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 20A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
17/32
16. EMC
The EMC behavior of the device is designed for applications in industrial environment as well as in residential,
commercial and light industry environments. The output is allowed to be grounded or floating.
The device is investigated according to EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 61000-6-4.
Without additional measures to reduce the conducted emissions on the output (e.g. by using a filter), the
device is not suited to supply a local DC power network in residential, commercial and light-industrial
environments. No restrictions apply for local DC power networks in industrial environments.
EMC Immunity
Electrostatic discharge EN 61000-4-2 Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field EN 61000-4-3 80MHz-2.7GHz 20V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Input lines
Output lines
Signal lines (coupling clamp)
4kV
2kV
2kV
Criterion A
Criterion A
Criterion A
Surge voltage on input EN 61000-4-5 L Æ N
L Æ PE, N Æ PE
2kV
2kV
*)
Criterion A
Criterion A
Surge voltage on output EN 61000-4-5 + Æ -
+ / - Æ PE
1kV
2kV
Criterion A
Criterion A
Surge voltage on DC-OK EN 61000-4-5 Signal lines Æ PE 1kV Criterion A
Conducted disturbance EN 61000-4-6 0.15-80MHz 20V Criterion A
Mains voltage dips EN 61000-4-11 0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
Criterion A
Criterion C
Criterion A
Criterion A
Criterion A
Criterion A
Voltage interruptions EN 61000-4-11 0% of 200Vac (=0V) 5000ms Criterion C
Powerful transients VDE 0160 Over entire load range 750V, 0.3ms Criterion A
*) 4kV are planned for June 2019
Performance criterions:
A: Device shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. The device may shut-down and restarts by itself. No damage or hazards for the device will occur.
EMC Emission
Conducted emission
input lines
EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B
Radiated emission EN 55011, EN 55022 Class B
Harmonic input current EN 61000-3-2 Fulfilled for Class A equipment
Fulfilled for Class C equipment
in the load range from 8 to 24A
Voltage fluctuations, flicker EN 61000-3-3 Fulfilled, tested with constant
current loads, non pulsing
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Switching Frequencies
PFC converter 100kHz Fixed frequency
Main converter 80kHz to 140kHz Output load dependent
Auxiliary converter 60kHz Fixed frequency