Datasheet
CP10.241, CP10.242, CP10.241-S1
CP-Series
24V, 10A, SINGLE PHASE INPUT
3. AC-INPUT
AC input nom. AC 100-240V suitable for TN-, TT- and IT mains networks
AC input range min. 85-264Vac continuous operation
min. 264-300Vac < 500ms
Allowed voltage L or N to earth max. 300Vac continuous, IEC 62103
Input frequency nom. 50–60Hz ±6%
Turn-on voltage typ. 80Vac steady-state value, see Fig. 3-1
typ. 55Vac dynamic value (250ms)
Shut-down voltage typ. 74Vac steady-state value, see Fig. 3-1
External input protection See recommendations in chapter 23.3.
AC 100V AC 120V AC 230V
Input current typ. 2.60A 2.15A 1.13A at 24V, 10A, see Fig. 3-3
Power factor
*)
typ. 0.99 0.99 0.97 at 24V, 10A, see Fig. 3-4
Crest factor
**)
typ. 1.5 1.5 1.65 at 24V, 10A
Start-up delay typ. 450ms 440ms 390ms see Fig. 3-2
Rise time typ. 30ms 30ms 30ms at 24V, 10A const. current load,
0mF load capacitance, see Fig. 3-2
typ. 75ms 75ms 75ms at 24V, 10A const. current load,
10mF load capacitance,, see Fig. 3-2
Turn-on overshoot max. 200mV 200mV 200mV see Fig. 3-2
External input protection See recommendations in chapter 23.3.
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
4/27
300Vac264V
Shut-down
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Jun. 2015 / Rev. 1.2 DS-CP10.241-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany