Datasheet

CP10.241, CP10.242, CP10.241-S1
CP-Series
24V, 10A, SINGLE PHASE INPUT
6. OUTPUT
Output voltage nom. 24V
Adjustment range min. 24-28V guaranteed
max. 30.0V
****)
at clockwise end position of potentiometer
Factory settings typ. 24.1V ±0.2%, at full load and cold unit
Line regulation max. 10mV 85-300Vac
Load regulation max. 50mV static value, 0A Æ 10A; see Fig. 6-1
Ripple and noise voltage max. 50mVpp 20Hz to 20MHz, 50Ohm
Output current nom. 10A at 24V, ambient temperature <60°C, see Fig. 6-1
nom. 12A
*)
at 24V, ambient temperature <45°C, see Fig. 15-1
nom. 7.5A at 24V and 70°C ambient temperature, see Fig. 15-1
nom. 8.6A at 28V, ambient temperature <60°C, see Fig. 6-1
nom. 10.3A
*)
at 28V, ambient temperature <45°C, see Fig. 15-1
nom. 6.45A at 28V and 70°C ambient temperature, see Fig. 15-1
typ. 30A up to at least 12ms
*****)
, output voltage stays above
20V, see Fig. 6-2 and Fig. 23-3, This peak current is
available once every five seconds (hardware
controlled).
Output power nom. 240W continuously available
nom. 288W
*)
Power Boost
*)
Overload behaviour cont. current output voltage > 13Vdc, see Fig. 6-1
Hiccup
PLUS
mode
**)
output voltage < 13Vdc, see Fig. 6-1
Short-circuit current min. 12.5A
***)
load impedance 45mOhm, see Fig. 6-3
max. 15.5A
***)
load impedance 45mOhm, see Fig. 6-3
max. 5A average (R.M.S.) current, load impedance 50mOhm,
see Fig. 6-3
min. 28A up to 12ms, load impedance 45mOhm, see Fig. 6-2
typ. 30.5A up to 12ms, load impedance 45mOhm, see Fig. 6-2
Output capacitance typ. 4 400μF included inside the power supply
*) Power Boost
This power/ current is continuously allowed up to an ambient temperature of 45°C.
Above 45°C, do not use this power/ current longer than a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes.
**) Hiccup
PLUS
Mode
At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 2s. After this, the
output is switched off for approx. 18s before a new start attempt is automatically performed. This cycle is repeated as long as the
overload exists. If the overload has been cleared, the device will operate normally. See Fig. 6-3
***) Discharge current of output capacitors is not included.
****) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not a
guaranteed value which can be achieved. The typical value is about 28.5V.
*****) Reduced pulse length for AC 100V mains.
Jun. 2015 / Rev. 1.2 DS-CP10.241-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/27