Datasheet

CP10.241, CP10.242, CP10.241-S1
CP-Series
24V, 10A, SINGLE PHASE INPUT
Fig. 3-3 Input current vs. output current at
24V output voltage
Fig. 3-4 Power factor vs. output current at
24V output voltage
12A
123456789
0
0.5
1.0
1.5
2.0
2.5
3A
Input Current, typ.
10 11
a) 100Vac
b) 120Vac
c) 230Vac
b
a
c
Output Current
Power Factor, typ.
123456789 12A
0.75
0.8
0.85
0.9
0.95
1.0
10 11
Output Current
(a) 100Vac,
(b) 120Vac,
(c) 230Vac
(a)
(b)
(c)
4. DC-INPUT
DC input nom. DC 110-150V ±20% CP10.241, CP10.241-S1
nom. DC 110-300V ±20% CP10.242
DC input range min. 88-187Vdc CP10.241, CP10.241-S1, continuous operation
min. 88-360Vdc CP10.242
DC input current typ. 2.35A at 110Vdc, at 24V, 10A
typ. 0.84A at 300Vdc, at 24V, 10A, CP10.242
Allowed Voltage L/N to Earth max. 375Vdc continuous, IEC 62103
Turn-on voltage typ. 80Vdc steady state value
Shut-down voltage typ. 74Vdc steady state value
Fig. 4-1 Wiring for DC Input
Instructions for DC use:
+
-
Load
L
PE
+
-
Power Supply
AC
Battery
N
DC
a) Use a battery or a similar DC source. A supply from the
intermediate DC-bus of a frequency converter is not
recommended and can cause a malfunction or damage
the unit.
b) Connect +pole to L and –pole to N.
c) Connect the PE terminal to an earth wire or to the
machine ground.
Jun. 2015 / Rev. 1.2 DS-CP10.241-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/27