Datasheet

CP10.241, CP10.242, CP10.241-S1
CP-Series
24V, 10A, SINGLE PHASE INPUT
16. PROTECTION FEATURES
Output protection Electronically protected against overload, no-load and short-circuits
*)
Output over-voltage protection typ. 30.5Vdc
max. 32Vdc
In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Degree of protection IP 20 EN/IEC 60529
For use in a controlled environment according to CSA
22.2 No 107.1-01.
Penetration protection > 4mm e.g. screws, small parts
Over-temperature protection yes Output shut-down with automatic restart
Input transient protection MOV (Metal Oxide Varistor)
Internal input fuse included not user replaceable
*) In case of a protection event, audible noise may occur.
17. SAFETY FEATURES
Input / output separation
*)
SELV IEC/EN 60950-1
PELV IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
double or reinforced insulation
Transformers fulfill IEC/EN 61558-2-16 Safety Isolating Transformers corresponding to Part 2-6
of the IEC/EN 61558
Class of protection I PE (Protective Earth) connection required
Isolation resistance > 5MOhm input to output, 500Vdc
PE resistance < 0.1Ohm PE terminal to housing
Touch current (leakage current) typ. 0.14mA / 0.36mA 100Vac, 50Hz, TN-,TT-mains / IT-mains
typ. 0.20mA / 0.50mA 120Vac, 60Hz, TN-,TT-mains / IT-mains
typ. 0.33mA / 0.86mA 230Vac, 50Hz, TN-,TT-mains / IT-mains
max. 0.18mA / 0.43mA 110Vac, 50Hz, TN-,TT-mains / IT-mains
max. 0.26mA / 0.61mA 132Vac, 60Hz, TN-,TT-mains / IT-mains
max. 0.44mA / 1.05mA 264Vac, 50Hz, TN-,TT-mains / IT-mains
*) double or reinforced insulation
Jun. 2015 / Rev. 1.2 DS-CP10.241-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany