Datasheet

CP10.241, CP10.241-C1, CP10.241-S1,
CP10.241-S2, CP10.242
CP-Series
24V, 10A, 240W, SINGLE PHASE INPUT
Aug. 2017 / Rev. 1.4a DS-CP10.241-EN
All values are typical at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/30
6. OUTPUT
Output voltage Nom. 24V
Adjustment range Min. 24-28V Guaranteed value
Max. 30.0V This is the maximum output voltage which can occur
at the clockwise end position of the potentiometer
due to tolerances. It is not a guaranteed value which
can be achieved.
Factory settings Typ. 24.1V ±0.2%, at full load and cold unit
Line regulation Max. 10mV Between 85 and 300Vac
Load regulation Max. 50mV Between 0 and 12A, static value, see Fig. 6-1
Ripple and noise voltage Max. 50mVpp Bandwidth 20Hz to 20MHz, 50Ohm
Output current Nom. 12A
1)
At 24V and an ambient temperature below 45°C,
see Fig. 16-1
Nom. 10A At 24V and 60°C ambient temperature, see Fig. 6-1
Nom. 7.5A At 24V and 70°C ambient temperature, see Fig. 16-1
Nom. 10.3A
1)
At 28V and an ambient temperature below 45°C,
see Fig. 16-1
Nom. 8.6A At 28V and 60°C ambient temperature, see Fig. 6-1
Nom. 6.45A At 28V and 70°C ambient temperature, see Fig. 16-1
Typ. 30A For minimal 12ms once every five seconds, see Fig. 6-2.
The output voltage stays above 20V. See chapter 24.1
for more peak current measurements. For AC 100V
mains, the pulse length is shorter than 12ms.
Overload behaviour Continuous current Output voltage above 13Vdc, see Fig. 6-1
Hiccup
PLUS
mode
2)
Output voltage below 13Vdc, see Fig. 6-1
Short-circuit current Min. 12.5A
3)
Load impedance <45mOhm, see Fig. 6-3
Max. 15.5A
3)
Load impedance <45mOhm, see Fig. 6-3
Max. 5A Average (R.M.S.) current, load impedance 50mOhm,
see Fig. 6-3
Min. 28A Up to 12ms, load impedance <45mOhm, see Fig. 6-2
Typ. 30.5A Up to 12ms, load impedance <45mOhm, see Fig. 6-2
Output capacitance Typ. 4 400μF Included inside the power supply
1) Power Boost
This power/ current is continuously allowed up to an ambient temperature of 45°C.
Above 45°C, do not use this power or current longer than a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes.
2) Hiccup
PLUS
Mode
At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 2s. After this, the
output is switched off for approx. 18s before a new start attempt is automatically performed. This cycle is repeated as long as the overload
exists. If the overload has been cleared, the device will operate normally. See Fig. 6-3
3) Discharge current of output capacitors is not included.