Datasheet
CP10.241, CP10.241-C1, CP10.241-S1,
CP10.241-S2, CP10.242
CP-Series
24V, 10A, 240W, SINGLE PHASE INPUT
Aug. 2017 / Rev. 1.4a DS-CP10.241-EN
All values are typical at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
3. AC-INPUT
AC input Nom. AC 100-240V Suitable for TN-, TT- and IT mains networks
AC input range Min. 85-264Vac Continuous operation
Min. 264-300Vac For maximal 500ms
Allowed voltage L or N to earth Max. 300Vac Continuous according to IEC 62477-1
Input frequency Nom. 50–60Hz ±6%
Turn-on voltage Typ. 80Vac Steady-state value, see Fig. 3-1
Shut-down voltage Typ. 70Vac Steady-state value, see Fig. 3-1
Typ. 55Vac Dynamic value for maximal 250ms
External input protection See recommendations in chapter 24.3.
AC 100V AC 120V AC 230V
Input current Typ. 2.60A 2.15A 1.13A At 24V, 10A, see Fig. 3-3
Power factor
*)
Typ. 0.99 0.99 0.97 At 24V, 10A, see Fig. 3-4
Crest factor
**)
Typ. 1.5 1.5 1.65 At 24V, 10A
Start-up delay Typ. 300ms 290ms 240ms See Fig. 3-2
Rise time Typ. 30ms 30ms 30ms At 24V, 10A const. current load,
0mF load capacitance, see Fig. 3-2
Typ. 75ms 75ms 75ms at 24V, 10A const. current load,
10mF load capacitance,, see Fig. 3-2
Turn-on overshoot Max. 200mV 200mV 200mV See Fig. 3-2
External input protection See recommendations in chapter 24.3.
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
300Vac264V
Shut-down
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
4/30