17. PROTECTION FEATURES
Output protection Electronically protected against overload, no-load and short-circuits. In case of a
protection event, audible noise may occur.
Output over-voltage protection Typ. 30.5Vdc
Max. 32Vdc
In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Degree of protection IP 20 EN/IEC 60529
Penetration protection > 4mm E.g. screws, small parts
Over-temperature protection Yes Output shut-down with automatic restart.
The temperature sensor is installed on critical
components inside the unit and turns the unit off in
safety critical situations, which can happen e.g. when
de-rating requirements are not observed, ambient
temperature is too high, ventilation is obstructed or
the de-rating requirements for different mounting
orientation is not followed. There is no correlation
between the operating temperature and turn-off
temperature since this is dependent on input voltage,
load and installation methods.
Input transient protection MOV
(Metal Oxide Varistor)
For protection values see chapter 15 (EMC).
Internal input fuse Included Not user replaceable slow-blow high-braking capacity
fuse
18. SAFETY FEATURES
Input / output separation Double or reinforced galvanic isolation
SELV IEC/EN 60950-1
PELV IEC/EN 60204-1, EN 62477-1, IEC 60364-4-41
Class of protection I PE (Protective Earth) connection required
Isolation resistance > 500MOhm At delivered condition between input and output,
measured with 500Vdc
> 500MOhm At delivered condition between input and PE,
measured with 500Vdc
> 500MOhm At delivered condition between output and PE,
measured with 500Vdc
> 500MOhm At delivered condition between output and DC-OK
contacts, measured with 500Vdc
PE resistance < 0.1Ohm Resistance between PE terminal and the housing in the
area of the DIN-rail mounting bracket.
Touch current (leakage current) Typ. 0.14mA / 0.36mA At 100Vac, 50Hz, TN-,TT-mains / IT-mains
Typ. 0.20mA / 0.50mA At 120Vac, 60Hz, TN-,TT-mains / IT-mains
Typ. 0.33mA / 0.86mA At 230Vac, 50Hz, TN-,TT-mains / IT-mains
Max. 0.18mA / 0.43mA At 110Vac, 50Hz, TN-,TT-mains / IT-mains
Max. 0.26mA / 0.61mA At 132Vac, 60Hz, TN-,TT-mains / IT-mains
Max. 0.44mA / 1.05mA At 264Vac, 50Hz, TN-,TT-mains / IT-mains