Datasheet

CP10.241, CP10.241-C1, CP10.241-S1,
CP10.241-S2, CP10.242
CP-Series
24V, 10A, 240W, SINGLE PHASE INPUT
Aug. 2017 / Rev. 1.4a DS-CP10.241-EN
All values are typical at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
Switching Frequencies
PFC converter 110kHz Fixed frequency
Main converter 84kHz to 140kHz Output load dependent
Auxiliary converter 60kHz Fixed frequency
16. ENVIRONMENT
Operational temperature
1)
-25°C to +70°C (-13°F to 158°F) Reduce output power according to Fig. 16-1
Storage temperature -40°C to +85°C (-40°F to 185°F) For storage and transportation
Output de-rating 3.2W/°C
6W/°C
Between +45°C and +60°C (113°F to 140°F)
Between +60°C and +70°C (140°F to 158°F)
Humidity 5 to 95% r.h. According to IEC 60068-2-30
Do not energize while condensation is present.
Vibration sinusoidal
2)
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
According to IEC 60068-2-6
Shock
2)
30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total
According to IEC 60068-2-27
Altitude 0 to 2000m (0 to 6 560ft) Without any restrictions
2000 to 6000m (6 560 to 20 000ft) Reduce output power or ambient
temperature, see Fig. 16-2.
Altitude de-rating 15W/1000m or 5°C/1000m Above 2000m (6500ft), see Fig. 16-2
Over-voltage category III According to IEC 62477-1 for altitudes up to
2000m
II According to IEC 62477-1 for altitudes from
2000m to 6000m
Degree of pollution 2 According to IEC 62477-1, not conductive
LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
Corrosive gases ISA-71.04-1985, Severity Level G3, IEC 60068-2-60 Test Ke Method 4
Audible noise Some audible noise may be emitted from the power supply during no load, overload or
short circuit.
1) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the unit.
2) Tested in combination with DIN-Rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard orientation.
Fig. 16-1 Output current vs. ambient temp. Fig. 16-2 Output current vs. altitude
Allowed Output Current at 24V
0
-25 0 20 40
70°C
2A
4A
6A
8A
10A
12A
60
A
Ambient Temperature
A... 85 to 264Vac, continuous
B... short term
B
0
0 2000m 4000m
6000m
2A
4A
6A
8A
10A
12A
Allowed Output Current at 24V
Altitude
B
C
A
.
.
.
T
a
m
b
<
6
0
°
C
B
.
.
.
T
a
m
b
<
5
0
°
C
C
.
.
.
T
a
m
b
<
4
0
°
C
D
.
.
.
S
h
o
r
t
t
e
r
m
A
D
16/30