Datasheet

CP10.241, CP10.241-C1, CP10.241-S1,
CP10.241-S2, CP10.242
CP-Series
24V, 10A, 240W, SINGLE PHASE INPUT
Aug. 2017 / Rev. 1.4a DS-CP10.241-EN
All values are typical at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
12/30
12. TERMINALS AND WIRING
The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring.
CP10.241, CP10.241-C1, CP10.242 Input Output DC-OK-Signal
Type Screw termination Screw termination Push-in termination
Solid wire Max. 6mm
2
Max. 6mm
2
Max. 1.5mm
2
Stranded wire Max. 4mm
2
Max. 4mm
2
Max. 1.5mm
2
American Wire Gauge AWG 20-10 AWG 20-10 AWG 24-16
Max. wire diameter (including ferrules) 2.8mm 2.8mm 1.6mm
Recommended tightening torque Max. 1Nm, 9lb-in Max. 1Nm, 9lb-in -
Wire stripping length 7mm / 0.28inch 7mm / 0.28inch 7mm / 0.28inch
Screwdriver 3.5mm slotted or cross-
head No 2
3.5mm slotted or cross-
head No 2
3mm slotted to open
the spring
CP10.241-S1 Input Output DC-OK-Signal
Type Quick-connect spring-
clamp termination
Quick-connect spring-
clamp termination
Push-in termination
Solid wire Max. 6mm
2
Max. 6mm
2
Max. 1.5mm
2
Stranded wire Max. 4mm
2
Max. 4mm
2
Max. 1.5mm
2
American Wire Gauge AWG 20-10 AWG 20-10 AWG 24-16
Max. wire diameter (including ferrules) 2.8mm 2.8mm 1.6mm
Wire stripping length 10mm / 0.4inch 10mm / 0.4inch 7mm / 0.28inch
Screwdriver - - 3mm slotted to open
the spring
CP10.241-S2 Input Output DC-OK-Signal
Type Push-in termination Push-in termination Push-in termination
Solid wire Max. 2.5mm
2
Max. 2.5mm
2
Max. 1.5mm
2
Stranded wire Max. 2.5mm
2
Max. 2.5mm
2
Max. 1.5mm
2
Stranded wire with ferrules Max. 1.5mm
2
Max. 1.5mm
2
Max. 1.5mm
2
American Wire Gauge AWG 24-12 AWG 24-12 AWG 24-16
Max. wire diameter (including ferrules) 2.3mm 2.3mm 1.6mm
Wire stripping length 10mm / 0.4inch 10mm / 0.4inch 7mm / 0.28inch
Screwdriver 3.0mm slotted to open
the spring
3.0mm slotted to open
the spring
3mm slotted to open
the spring
Instructions for wiring:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C and
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Unused terminal compartments should be securely tightened.
e) Ferrules are allowed.