User manual
EN
CP10.241 Instruction Manual
The information in this document is believed to be accurate and reliable and may change without notice
Product Description
The CP10.241 is a DIN-rail mountable single-phase-input power supply of the DIMENSION series. It
provides a floating, stabilized and galvanically separated SELV/PELV output voltage.
The CP10.241-C1 device is the same as the CP10.241 but with conformal coated pc-boards.
Intended Use
This device is designed for installation in an enclosure and is intended for general use such as in
industrial control, office, communication, and instrumentation equipment. Do not use this device in
equipment, where malfunction may cause severe personal injury or threaten human life.
Installation Notes
- This device does not contain serviceable parts. The tripping of an internal fuse is caused by an
internal defect. If damage or malfunction should occur during installation or operation, immediately
turn power off and send the device to the factory for inspection.
- Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
- Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of
the device. For other orientations see de-rating requirements in the datasheet.
- Make sure that the wiring is correct by following all local and national codes. Use appropriate
copper cables that are designed for a minimum operating temperature of 60°C for ambient
temperatures up to +45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient
temperatures up to +70°C. Ensure that all strands of a stranded wire enter the terminal connection.
- Unused screw terminals should be securely tightened.
- For use in a controlled environment. Do not use the device in pollution degree 3 areas without
additional protection or in applications where a degree of protection better than IP20 is required.
- The device is suitable to be supplied from TN-, TT- and IT mains networks. The voltage between
the L or N terminal and the PE terminal must not exceed 300Vac continuously acc. to IEC 62477-1.
- The device is designed for use in overvoltage category II zones according to IEC 60950-1 or UL
508 and overvoltage category III zones according to IEC 62477-1.
- The input can also be powered from batteries or similar DC sources. The voltage between the (+)
or (-) terminal and the PE terminal must not exceed 375Vdc continuously acc. to IEC 62477-1.
- A disconnecting means shall be provided for the input or output of the device when used in
applications according to CSA C22.2 No 107.1-01 or CSA C22.2 No 107.1-16.
- The device is designed as “Class of Protection I” equipment according to IEC 61140. A PE
(Protective Earth) connection is required.
- The output is electronically protected against no-load, overload and short circuit and can supply any
kind of loads, including unlimited inductive loads and capacitive loads up to 1.5F.
- Do not apply return voltages from the load to the output higher than 35V.
- The device is designed for convection cooling and does not require an external fan. Do not obstruct
airflow and do not cover ventilation grid (e.g. cable conduits) by more than 15%!
- The device is designed for altitudes up to 6000m. See details in the product datasheet for additional
requirements above 2000m.
- Keep the following minimum installation clearances when the device is permanently loaded with
more than 50% of the nominal current: 40mm on top, 20mm on the bottom, 5mm left and right side.
Increase the 5mm to 15mm in case the adjacent device is a heat source.
- The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL)
without additional protection device. If an external fuse is utilized, do not use circuit breakers
smaller than 6A B- or C-Characteristic to avoid a nuisance tripping of the circuit breaker.
- The maximum surrounding air temperature is +70°C / +158°F. The operational temperature is the
same as the ambient or surrounding air temperature and is defined as the air temperature 2cm
below the device.
- For suitable accessories, such as mounting brackets or supplementary devices, see product datasheet.
Installation Notes for Hazardous Location Areas
The device is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II
Category 3 (Zone 2) environments.
WARNING EXPLOSION HAZARDS!
- Substitution of components may impair suitability for this environment. Do not disconnect the
device or operate the voltage adjustment unless power has been switched off or the area is known
to be non-hazardous.
- A suitable enclosure must be provided for the end product which has a minimum protection of IP54
and fulfils the requirements of the EN 60079-15.
Functional Description
- The output voltage can be adjusted with a small flat-blade screwdriver behind the flap on the front.
- The green DC-OK LED reports an output voltage above 90% of the adjusted output voltage of a running
device.
- The DC-OK relay monitors the output voltage and the contact is closed, when the DC-OK LED is on.
Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads.
- The device is equipped with an over-temperature protection. In case of a high temperature, the
output shut-down and starts automatically again after cooling off.
- The device is equipped with the Hiccup
PLUS
overload characteristic. At heavy overloads (when
output voltage falls below 13V), the device delivers continuous output current for 2s. After this, the
output is switched off for approx. 18s before a new start attempt is automatically performed. This
cycle is repeated as long as the overload exists. When cleared, the device will operate normally.
- Devices can be paralleled to increase the output power. The output voltage shall be adjusted to the
same value (±100mV) with the same load conditions on all devices, or the devices can be left with
the factory settings. The ambient temperature is not allowed to exceed +40°C. If more than three
devices are connected in parallel, a diode, fuse or circuit breaker with a rating of 15A or 16A is
required on each output.
- Devices of the same type can be connected in series for higher output voltages. It is possible to
connect as many devices in series as needed, providing the sum of the output voltage does not
exceed 150Vdc. Avoid return voltages from the load to the output.
- In case of an internal defect, a redundant circuit limits the maximum output voltage to 32V. The
output shuts down and automatically attempts to restart.
Technical data
A
ll parameters are typical values specified at 230Vac input voltage, 24V
10A output, 25°C ambient temperature and after a 5 minutes run-in time
unless otherwise noted.
Output voltage DC 24V Nominal
Adjustment range 24 – 28Vdc Factory setting 24.1V
Output current 12.0 – 10.3A Below +45°C ambient
10.0 – 8.6A At +60°C ambient
7.5 – 6.5A At +70°C ambient
Derate linearely between +45°C and +70°C
Input voltage AC
A
C 100 - 240V -15% / +10%
Mains frequency 50 – 60Hz ±6%
Input current AC 2.15 / 1.13A At 120 / 230Vac
Power factor 0.99 / 0.97 At 120 / 230Vac
Input voltage DC DC 110 - 150V ±20%
Input current DC 2.35A At 110Vdc
Input inrush current 6 / 9A pk At 40°C, 120 / 230Vac
Efficiency 93.6 / 95.2% At 120 / 230Vac
Power losses 16.4 / 12.1W At 120 / 230Vac
Hold-up time 37ms
Temperature range -25 to +70°C
Maximum wire size
1)
6mm² / 4mm² Power terminals
Wire size AWG
A
WG 20-10 Power terminals
Maximum wire diameter
2)
2.8mm Power terminals
Wire stripping length 7mm / 0.28inch Power terminals
Tightening torque 1Nm / 9lb.inch Power terminals
Maximal wire size
1)
1.5mm² / 1.5mm² DC-OK terminals
Wire size AWG
A
WG 24-16 DC-OK terminals
Maximal wire diameter
2)
1.6 mm DC-OK terminals
Wire stripping length 7mm / 0.28inch DC-OK terminals
Size (wxhxd) 39x124x117mm Without DIN-rail
Weight 600g / 1.3lb
1) Solid / stranded wire 2) Including ferrules
Functional diagram
+
+
-
-
Output
Over-
Voltage
Protection
PFC
Converter
Voltage
Regulator
Power
Converter
Output
Filter
Output
Power
Manager
Temper-
ature
Shut-
down
Input Fuse
Input Filter
Input Rectifier
Inrush Current
Limiter
V
OUT
L
N
DC-OK
Contact
DC-OK
LED
DC-ok
Relay
-
13
14
Output characteristic
A
Output voltage
15A
24V
Output current
12V
0V
3A 6A 9A 12A0A
Adjustment range
28V
Hiccup
PLUS
mode
B
A: continuous current
B: intermitted current
Temperature range
Allowed output current at 24V
Ambient temperature
0A
-25
A: continuous
B: short term (max. 60s)
12A
+250 +45 +70°C
7.5A
A
B
10A
+60
Headquarters: PULS GmbH, Elektrastr. 6, 81925 Munich, Germany, www.pulspower.com
German
y
+49 89 9278 0
China +86 512 62881820
France +33 478 668 941
North America +1 630 587 9780
A
ustria +43 2764 3213
Singapore +65 6684 2310
Switzerland +41 56 450 18 10
United Kingdom +44 1525 841001