Data Sheet
Table Of Contents
- 1. Intended Use
- 2. Installation Requirements
- 3. AC-Input
- 4. DC-Input
- 5. Input Inrush Current
- 6. Output
- 7. Hold-up Time
- 8. DC-OK Relay Contact
- 9. Efficiency and Power Losses
- 10. Lifetime Expectancy
- 11. MTBF
- 12. Terminals and Wiring
- 13. Functional Diagram
- 14. Front Side and User Elements
- 15. EMC
- 16. Environment
- 17. Protection Features
- 18. Safety Features
- 19. Dielectric Strength
- 20. Approvals
- 21. Other Fulfilled Standards
- 22. Physical Dimensions and Weight
- 23. Accessories
- 24. Application Notes
- 24.1. Peak Current Capability
- 24.2. Back-feeding Loads
- 24.3. External Input Protection
- 24.4. Output Circuit Breakers
- Series Operation
- Parallel Use to Increase Output Power
- 24.7. Parallel Use for Redundancy
- 24.8. Inductive and Capacitive Loads
- 24.9. Charging of Batteries
- Operation on Two Phases
- 24.11. Use in a Tightly Sealed Enclosure
- 24.12. Mounting Orientations
CP10.241, CP10.241-C1, CP10.241-S1,
CP10.241-S2, CP10.242
CP-Series
24V, 10A, 240W, SINGLE PHASE INPUT
Aug. 2017 / Rev. 1.4a DS-CP10.241-EN
All values are typical at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
Fig. 6-1 Output voltage vs. output current,
typ.
Fig. 6-2 Dynamic output current capability,
typ.
Output Voltage
0
0 12.5
4
8
12
28V
16
20
24
20A7.52.5 5 10 15 17.5
Adjustment
Range
Output Current
Continuous
current
Factory
setting
Hiccup
PLUS
mode
Output Voltage
(dynamic behavior, < 12ms)
0
0
4
8
12
28V
16
20
24
50A2010 30 40515253545
Adjustment
Range
Output Current
Fig. 6-3 Short-circuit on output, Hiccup
PLUS
mode, typ.
Output
Current
0
14A
18s
18s
18s
2s
2s
2s
t
Short -circuit
Normal
operation
Normal
operation
7. HOLD-UP TIME
AC 100V AC 120V AC 230V
Hold-up Time Typ. 73ms 73ms 73ms At 24V, 5A, see Fig. 7-1
Min. 55ms 55ms 55ms At 24V, 5A, see Fig. 7-1
Typ. 37ms 37ms 37ms At 24V, 10A, see Fig. 7-1
Min. 28ms 28ms 28ms At 24V, 10A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down ehaviour, definitions
0
10
20
30
40
80ms
90 120 155 190 230Vac
Input Voltage
50
60
Hold-up Time
70
a
b
c
d
a) 24V 5A typ.
b) 24V 5A min.
c) 24V 10A typ.
d) 24V 10A min.
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
8/30