Data Sheet
Table Of Contents
- 1. Intended Use
- 2. Installation Requirements
- 3. Input Voltage
- 4. Soft-start and Input Inrush Current Surge
- 5. Output
- 6. Hold-up Time
- 7. Efficiency and Power Losses
- 8. Functional Diagram
- 9. Front Side and User Elements
- 10. Terminals and Wiring
- 11. Reliability
- 12. EMC
- 13. Environment
- 14. Protection Features
- 15. Safety Features
- 16. Dielectric Strength
- 17. Approvals
- 18. RoHS, REACH and Other Fulfilled Standards
- 19. Physical Dimensions and Weight
- 20. Accessories
- 21. Application Notes
- 21.1. Peak Current Capability
- 21.2. Back-feeding Loads
- 21.3. Inductive and Capacitive Loads
- 21.4. External Input Protection
- 21.5. Requirements for the Supplying Source
- 21.6. Parallel Use to Increase Output Power
- 21.7. Parallel Use for Redundancy
- 21.8. Series Operation
- 21.9. Charging of Batteries
- 21.10. Use in a Tightly Sealed Enclosure
- 21.11. Mounting Orientations
CD5.241-L1
CD-Series
DC/DC Converter 24V, 3.8A
7. EFFICIENCY AND POWER LOSSES
Input 24Vdc
Efficiency typ. 90.5% at 24V, 3.8A
Power losses typ. 0.7W at no output load
typ. 5.5W at 24V, 1.9A
typ. 9.7W at 24V, 3.8A
Fig. 7-1 Efficiency vs. output current at 24V,
typ.
Fig. 7-2 Losses vs. output current at 24V,
typ.
Efficiency
8/21
1
86
88
90
85
91%
4
A
233.52.5
87
89
1.50.5
Output Current
Power Losses
012 4
A
0
2
6
10
12W
4
3
8
Output Current
Fig. 7-3 Efficiency vs. input voltage at 24V,
3.8A, typ.
Fig. 7-4 Losses vs. input voltage at 24V, 3.8A,
typ.
Efficiency
18 20 22 26 28 32Vd
c
91%
88.5
89.5
90.5
90.0
89.0
88.0
24 30
Input Voltage
Power Losses
0
2
4
6
8
10
12W
18 20 24 26 28 32Vd
Input Voltage
22 30
c
Mar. 2016 / Rev. 1.2 DS-CD5.241-L1-EN
All parameters are specified at 24V, 3.8A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany