Data Sheet
Table Of Contents
- 1. Intended Use
- 2. Installation Requirements
- 3. Input Voltage
- 4. Soft-start and Input Inrush Current Surge
- 5. Output
- 6. Hold-up Time
- 7. Efficiency and Power Losses
- 8. Functional Diagram
- 9. Front Side and User Elements
- 10. Terminals and Wiring
- 11. Reliability
- 12. EMC
- 13. Environment
- 14. Protection Features
- 15. Safety Features
- 16. Dielectric Strength
- 17. Approvals
- 18. RoHS, REACH and Other Fulfilled Standards
- 19. Physical Dimensions and Weight
- 20. Accessories
- 21. Application Notes
- 21.1. Peak Current Capability
- 21.2. Back-feeding Loads
- 21.3. Inductive and Capacitive Loads
- 21.4. External Input Protection
- 21.5. Requirements for the Supplying Source
- 21.6. Parallel Use to Increase Output Power
- 21.7. Parallel Use for Redundancy
- 21.8. Series Operation
- 21.9. Charging of Batteries
- 21.10. Use in a Tightly Sealed Enclosure
- 21.11. Mounting Orientations
CD5.241-L1
CD-Series
DC/DC Converter 24V, 3.8A
13. ENVIRONMENT
Operational temperature
*)
-25°C to +70°C (-13°F to 158°F) see Fig. 13-1
Storage temperature -40 to +85°C (-40°F to 185°F) for storage and transportation
Humidity
**)
5 to 95% r.H. IEC 60068-2-30
Vibration sinusoidal
***)
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
IEC 60068-2-6
Shock
***)
30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude 0 to 6000m (0 to 20 000ft) Reduce output power or ambient temperature
above 2000m sea level.
Altitude de-rating 5.8W/1000m or 5°C/1000m above 2000m (6500ft), see Fig. 13-2
Over-voltage category III IEC 62477-1, EN 50178, altitudes up to 2000m
II Altitudes from 2000m to 6000m
Degree of pollution 2 IEC 62477-1, EN 50178, not conductive
LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
**) Do not energize while condensation is present
***) Tested in combination with DIN-Rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard mounting
orientation.
Fig. 13-1 Output current vs. ambient temp. Fig. 13-2 Output current vs. altitude at 24V
0
12/21
-25 0 20 40
70°
C
1
2
3
4A
60
Ambient Temperature
Allowable Output
Current
0
0 2000 4000
6000m
1
2
3
4A
Altitude
A
.
.
.
T
a
m
b
<
7
0
°
C
B
.
.
.
T
a
m
b
<
6
0
°
C
B
A
Allowable Output
Current
Mar. 2016 / Rev. 1.2 DS-CD5.241-L1-EN
All parameters are specified at 24V, 3.8A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany