Datasheet
CD10.482
CD-Series
DC/DC Converter 48V/48V, 5A, 240W
PRELIMINARY
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and right side.
Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device is permanently loaded with
less than 50%, the 5mm can be reduced to zero.
The device is designed, tested and approved for branch circuits up to 50A without additional protection device. If an
external fuse is utilized, do not use circuit breakers smaller than 10A B- or C-Characteristic to avoid a nuisance tripping
of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the same as the ambient
or surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
July 2018 / Rev. 0.1 DS-CD10.482-EN All values are typical figures specified at 48Vdc input voltage 48V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany