Datasheet
CD10.482
CD-Series
DC/DC Converter 48V/48V, 5A, 240W
PRELIMINARY
1. INTENDED USE
This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control,
process control, monitoring and measurement equipment or the like.
Do not use this device in equipment where malfunction may cause severe personal injury or threaten human life.
2. INSTALLATION INSTRUCTIONS
WARNING
Risk of electrical shock, fire, personal injury or death.
- Turn power off before working on the device. Protect against inadvertent re-powering.
- Do not modify or repair the unit.
- Do not open the unit as high voltages may present inside.
- Use caution to prevent any foreign objects from entering the housing.
- Do not use in wet locations or in areas where moisture or condensation can be expected.
- Do not touch during power-on, and immediately after power-off. Hot surface may cause burns.
Obey the following installation requirements:
This device may only be installed and put into operation by qualified personnel.
This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to
the factory for inspection.
Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the device. Other
mounting orientations require a reduction in output current.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper cables that are
designed for a minimum operating temperature of 60°C for ambient temperatures up to +45°C, 75°C for ambient
temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. Ensure that all strands of a stranded wire
enter the terminal connection.
Unused screw terminals should be securely tightened.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or frost allowed.
The enclosure of the device provides a degree of protection of IP20.
The input can be powered from batteries or similar DC sources. The voltage between the input terminals and ground
must not exceed 60Vdc continuously. The ripple voltage in the low frequency range between 50Hz and 10kHz must be
negligible when used in marine applications.
The input must be powered from a PELV or SELV source or an "Isolated Secondary Circuit" in order to maintain a SELV
or PELV output.
Check for correct input polarity. The device will not operate when the voltage is reversed.
A disconnecting means shall be provided for the input of the device.
The device is designed as “Class of Protection III” equipment according to IEC 61140.
A PE (ground) connection is not required. However, connecting the chassis ground terminal to ground can be
beneficial to gain a high EMI immunity.
The device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not
cover ventilation grid!
The device is designed for altitudes up to 6000m (19685ft). See additional requirements in this document for use above
2000m (6560ft).
July 2018 / Rev. 0.1 DS-CD10.482-EN All values are typical figures specified at 48Vdc input voltage 48V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
3/27