Datasheet

CD10.482
CD-Series
DC/DC Converter 48V/48V, 5A, 240W
PRELIMINARY
14. EMC
The EMC behavior of the device is designed for applications in industrial environment as well as in residential,
commercial and light industry environments.
The device is investigated according to the generic standards EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 61000-
6-4.
EMC Immunity
Electrostatic discharge EN 61000-4-2 Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field EN 61000-4-3 80MHz-2.7GHz 20V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Input lines
Output lines
4kV
2kV
Criterion A
Criterion A
Surge voltage on input EN 61000-4-5 + Æ - 1kV Criterion A
+/- Æ chassis ground
2kV Criterion A
Surge voltage on output EN 61000-4-5 + Æ -
+ / - Æ chassis ground
500V
1kV
Criterion A
Criterion A
Conducted disturbance EN 61000-4-6 0.15-80MHz 20V Criterion A
Criterions:
A: The device shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. The device may shut down and restarts by itself. No damage or hazards for the device will occur.
EMC Emission
Conducted emission on
input lines
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 Limits for DC power networks
according to EN 61000-6-3
fulfilled
Conducted emission on
output lines
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 T.B.D.
Radiated emission EN 55011, EN 55022 Class B
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Switching Frequency
Main converter 75kHz to 500kHz Output load and input voltage dependent
July 2018 / Rev. 0.1 DS-CD10.482-EN All values are typical figures specified at 48Vdc input voltage 48V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
14/27