Datasheet

CD10.241
CD-Series
DC/DC Converter 24V/24V, 10A, 240W
14. ENVIRONMENT
Operational temperature
1)
-25°C to +70°C (-13°F to 158°F) reduce output power according Fig. 14-1
Storage temperature -40 to +85°C (-40°F to 185°F) for storage and transportation
Output de-rating 3.2W/°C 45-60°C (113°F to 140°F)
6W/°C 60-70°C (140°F to 158°F)
Humidity
2)
5 to 95% r.H. IEC 60068-2-30
Vibration sinusoidal
3)
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
IEC 60068-2-6
Shock
3)
30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude 0 to 6000m (0 to 20 000ft) reduce output power or ambient temperature
above 2000m sea level.
Altitude de-rating 15W/1000m or 5°C/1000m above 2000m (6500ft), see Fig. 14-2
Over-voltage category not applicable The concept of the overvoltage category is
used for equipment energized directly from
the low voltage mains (IEC 60664-1 §4.3.3.2.1).
Degree of pollution 2 IEC 62477-1, not conductive
LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
Corrosive gases ISA-71.04-1985, Severity Level G3, IEC 60068-2-60 Test Ke Method 4
Audible noise Some small audible noise will be emitted from the power supply.
1) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
2) Do not energize while condensation is present
3) Tested in combination with DIN-Rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard mounting
orientation. Higher levels allowed when using the wall mounting bracket ZM2.WALL.
Fig. 14-1 Output current vs. ambient temp. Fig. 14-2 Output current vs. altitude at 24V
0
-25 0 20 40
70°C
2
4
6
8
10
12A
60
Ambient Temperature
c
o
n
t
i
n
u
o
u
s
s
h
o
r
t
t
e
r
m
Allowable Output
Current at 24V
0
0 2000 4000
6000m
2
4
6
8
10
12A
Altitude
A
.
.
.
T
a
m
b
<
6
0
°
C
B
.
.
.
T
a
m
b
<
5
0
°
C
C
.
.
.
T
a
m
b
<
4
0
°
C
C
B
A
s
h
o
r
t
t
e
r
m
Allowable Output
Current at 24V
Apr. 2018 / Rev. 1.2 DS-CD10.241-EN All parameters are typical values at 24V, 10A, 24Vdc input voltage, 25°C ambient and
after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
13/25