Datasheet

CD10.241
CD-Series
DC/DC Converter 24V/24V, 10A, 240W
10. TERMINALS AND WIRING
Input Output
Type screw terminals screw terminals
Solid wire max. 6mm
2
max. 6mm
2
Stranded wire max. 4mm
2
max. 4mm
2
American Wire Gauge 20-10 AWG 20-10 AWG
Max. wire diameter 2.8mm (including ferrules) 2.8mm (including ferrules)
Wire stripping length 7mm / 0.275inch 7mm / 0.275inch
Screwdriver 3.5mm slotted or
Pozidrive No 2
3.5mm slotted or
Pozidrive No 2
Recommended tightening torque 1Nm, 9lb.in 1Nm, 9lb.in
Instructions:
a) Use appropriate copper cables that are designed for an operating temperature of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C and
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Screws of unused terminal compartments should be securely tightened.
Daisy chaining of outputs:
Daisy chaining (jumping from one DC/DC-converter output to the next) is allowed as long as the average output
current through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal
block.
Fig. 10-1 Daisy chaining of outputs Fig. 10-2 Using distribution terminals
DC/DC
Converter
+ +
- -
Input
Output
Load
+
-
max 25A!
DC/DC
Converter
+ +
- -
Input
Output
Load
+
-
Distribution
Terminals
DC/DC
Converter
+ +
- -
Input
Output
DC/DC
Converter
+ +
- -
Input
Output
Apr. 2018 / Rev. 1.2 DS-CD10.241-EN All parameters are typical values at 24V, 10A, 24Vdc input voltage, 25°C ambient and
after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
10/25