Specifications

9
ON
1 2 3 4 5 6
CN-LK
JP-LK
JP_LK
1 2 3 4 5 6
ON
CN-LK
RS-485
SET
RS-485
SET
Door Station Lock Connections
+12V
T/R -
LK - (GND)
LK+(COM)
N.O.
EB+
EB -
T/R+
PROR11
Connection Board
+12V
T/R -
L1
L2
PA
1
2
LK - (GND)
LK+(COM)
N.O.
EB+
EB -
T/R+
3
PB
L1 L2
PA
1
2
3
PB
BUS
BUS
1. Direct lock connection
Use the power of the system to supply for the electronic lock, so that the lock can connect to the Door Station directly,
without a additional power supply for the electronic lock. Note that the Door Station can only output a 12Vdc power,
therefore the kind of lock used is limited.
The rated power of the lock must be less than 12Vdc 300mA when using direct lock connection
method.
The GND must connect to the negative of the lock, and the COM connect to the positive .
Jumper set to 1
-
2 position for Power
-
to
-
Unlock safety type; set to 2
-
3 position for Power
-
off
-
to
-
Unlock type(in
this case the Unlock Relay mode should be set to Normally Closed on CHALLENGER PRO CONFIG
software)
The 5th bit of the DIP switches is for the unlocking time setting, it's set to off by default, for 1 second unloking
time. If set this bit to on, the unlocking time is 5 seconds.
If different unlocking time is needed to be configured, the CHALLENGER PRO CONFIG software can be
used to change the
Unlock Timing on the Parameter tab(see the program section).
A. Connection for Power
-
to
-
Unlock
type:
-
+
12V 300mA
Jumper set to 1-2 position
+12V
LK - (GND)
LK+(COM)
N.O.
EB+
EB -
1
2
3
DIPS
DIPS-5: default set to off,
unlocking time is 1 second.
(In most cases, 1 second is
work for Power-to-Unlock type)