Datasheet
ModuleType
Pick the correct module type for this slot.
ModuleClass
Pick the Proview Profinet module class for this slot. The class PnModule will be valid for all types
of modules. If this is picked, IO channels will automatically be created as children to the PnModule-
object corresponding to the data area for this module. In many cases there exist prepared subclasses
of the PnModule-class for the specific module. This is for example the case for a Siemens ET200M
device. For the prepared classes the IO channels will exist as a part of the module-object. The
prepared classes should be used if they exist.
ModuleInfo
Information about the module.
Subslot X
On some types of modules there are some parameters that can be set that will define the behaviour
of the subslot. Very often there is nothing to configure for the subslots.
When all the slots are configured you save by clicking on 'Ok' and leave by clicking 'Cancel'. The
moduleobjects with specified objectnames and classes are now created below the slave object.