User Manual

NLII-RH+T-SX |
Combined RH/temperature sensor with SIGFOX
4/6
Protronix s.r.o., Pardubická 177, Chrudim 537 01, Czech Republic www.protronix.cz/en/ www.careforair.eu/en/
User manual
um-nlii-rh+t-sx-en-v4-201103.docx
Jumpers on the electronics board
Factory settings
LED indication: by RH, indication turns off
when ambient light dims
T analog output: voltage output
RH analog output: voltage output
Mark
Description
Settings
Meaning
JP1
Current output offset RH
- shift quiescent current from 0 mA to 4 mA
current output RH 0-20 mA
current output RH 4-20 mA
JP2
Current output offset T
- shift quiescent current from 0 mA to 4 mA
current output T 0-20 mA
current output T 4-20 mA
JP3
Voltage/current output T
- select the type of analog output
- if voltage output T is selected,
JP2 must not be shorted
voltage output T
current output T
JP4
Voltage/current output RH
- select the type of analog output
- if voltage output RH is selected,
JP1 must not be shorted
voltage output RH
current output RH
JP6 - 1
LED indication
- LED indication according to ambient light -
when ambient light is dimmed (at night),
LED indicators turn off automatically.
permanent LED indication enabled
LED indication according to ambient light