Technical data

21
To replace pump
Drain down heating circuit only of boiler as follows:
From below boiler, close isolating valves on flow and
return connections to boiler.
Open boiler drain valve on left hand side of hy-
draulic block.
Note: It is not necessary to drain down entire heat-
ing circuit to carry out this work.
Simplification: for simpler work remove gas valve
module and right side cover.
Disconnect pump cable.
Remove 2 clips fixing pump, see diagram 20.
Unscrew 2 screws securing the pump to boiler
bottom.
Lift up the pipe and remove pump by lifting forward and out of boiler.
Fit replacement pump in reverse order to removal.
Open isolating valves on flow and return connections.
Refill, vent and pressurise boiler. Check for leaks.
To replace safety valve
Drain down heating circuit of boiler as described previously.
Simplification: for simpler work remove gas valve module and pump as described previously.
Remove expansion vessel hose from hydraulic block.
Remove draining pipe from safety valve and unscrew safety valve.
Fit replacement safety valve in reverse order to removal.
Important: Seal the safety valve thread by jointing compound.
To replace domestic heat exchanger
Drain down heating circuit of boiler as described previ-
ously.
Drain down hot water circuit of boiler as follows:
From below of boiler, close cold water inlet isolating valve.
Open a hot tap to drain hot water circuit.
Remove gas valve.
Unclip pump and pull forwards.
Disconnect expansion flexible hose at connection to
vessel fixing.
Remove fixing screws and plate exchanger over hydrau-
lic block, see diagram 21.
Fit replacement heat exchanger in reverse order to remov-
al, ensuring seals are correctly positioned in hydraulic
block.
Open isolating valves on flow and return connections,
refill, vent and pressurise boiler. Check for leaks.
Open cold water isolating valve. Check for leaks.
To replace overheat thermostats
Important: Isolate boiler from electrical supply before this
operation – connections to overheat thermostats are
mains voltage.
Locate overheat thermostats (a) and (c) to left hand side
of sealed chamber above thermistor, see diagram 22.
Unclip thermostat from pipe.
Pull off electrical connections from thermostat.
Fit replacement thermostat in reverse order to removal.
Note: No heat sink compound is required. The polarity of
the connections is not important.
Diagram 21
Diagram 20
Diagram 22