Specifications

Level One: Protege GX Installer Study Guide | August 2013 93
Example: Three Cars with Different Floor Ranges
Now let's look at an example where there are two lifts covering from Ground to Level 24, and a goods lift
covering the Basement to Level 24. The end user would also like Destination Reporting.
You would need:
1 System Controller
2 PRT-RDI2 or PRT-RDE2 modules
5 PRT-PX16 modules
5 PRT-PX16-DRI modules
3 Card Readers
The PRT-PX16 modules would be configured to control the following:
#1: Goods Lift, Floors B-15 (16 total)
#2: Goods Lift, Floors 16-24 (9 total)
#3: Lift 1, Floors 1-16 (16 total) - the ground Floor does not need to be controlled
#4: Lift 2, Floors 1-16 (16 total)
#5: Lifts 1 & 2, Floors 17-24 (16 total)
PRT-PX16-DRI
PRT-PX16-PCB
Goods Lift
Floors B, 1-15
PRT-PX16-DRI
PRT-PX16-PCB
Goods Lift
Floors 16-24
PRT-PX16-DRI
PRT-PX16-PCB
Lift 1
Floors 1-16
PRT-PX16-DRI
PRT-PX16-PCB
Lift 2
Floors 1-16
PRT-PX16-DRI
PRT-PX16-PCB
Lift 1, Floors 17-24
Lift 2, Floors 17-24
Primary Network
Secondary Network
Wiegand Connection
PRT-RDI2-PCB
PRT-RDI2-PCB
Goods Lift Lift 2Lift 1
PRT-CTRL-DIN