Specifications

68 Module 124: Protege GX Hardware Overview | The Protege PCB Range
Protege Standard 2 Reader Expander (PRT-RDS2)
The RDS2 has all the same functionality as the RDM2, but including a local power supply and battery backup, 2
additional zone inputs and 2 fixed voltage, high current monitored lock outputs. Power locks directly from the
module, or use the onboard Form C relays to switch an external power supply.
Technical Specifications:
Operating Current: 119mA (207mA max all relays activated)
AC Input: 16VAC, 40VA
DC Output (Aux): 1.2A Fused & Monitored
PSU: Local monitored PSU with battery backup
Doors: 2 doors, up to 4 readers in multiplex mode
Inputs: 8 4 state, EOL configurable. 1 module tamper
Outputs: 2 12VDC monitored lock outputs (1A continuous, 1.2A
max) or 2 Form C relays outputs for lock control (no lock monitoring),
6 open collector outputs (50mA)
Offline Operation: Stores first 10 users + 50 cached users. No
offline schedules. No offline event storage
Comms: 1 Galvanic isolated RS-485 port
Maximum Number per Enclosure
Medium Large Fatboy Jumbo
- 1 2 4
Requires 1 16VAC, 40VA 16 Transformer (TFR-40-16)