410 Module 138: Programming Walkthrough | Step by Step Tasks
5. Add a new trouble input named MEL PSU Tamper
Set the Module Type to Analog (AE)
Set the Module Address to 1
Set the Module Input to 1
6. Add the remaining Trouble Inputs from the table as shown (excluding 7), adjusting the name and setting the
Module Input number accordingly. For instance MEL PSU Mains Failure should be Module Input 2.
Input Number Description
AExxx:01 Module Tamper
AExxx:02 Mains Failure
AExxx:03 Low Battery / Battery Failure
AExxx:04 Output Voltage Low
AExxx:05 Output Over Current Failure
AExxx:06 Core Temperature Over Temp Failure
AExxx:07 Reserved
AExxx:08 Module Offline
7. Add the new trouble inputs to the All Trouble Inputs Status List:
Navigate to Monitoring | Setup | Status Lists and select All Trouble Inputs
Click Add to open the Select Devices window
Set the Device Type to Trouble Zone and choose your Controller
Select the PSU Trouble Inputs and click OK.
8. Wire the tamper input closed.
Task 17: Adding Trouble Inputs to the System Area
1. Select all the trouble inputs (CTRL+A) then click the Areas and Input Types tab
2. Set the first Area to the System area
3. Set the first Input Type to Trouble Silent
4. Click Save to update the records