Specifications

356 Module 136: System Monitoring | IP Monitoring
Configure the Report IP Service
1. Navigate to Programming | Services
2. Select your Controller then click Add to create a new service
3. Set the Service Type to Report IP
4. Set the Service Mode to Start with Controller. This ensures that the service is started automatically
whenever power is cycled to the controller. If left at Manual Mode, the service will need to be manually
starting each time the controller is reset or restarted.
5. Select the General tab:
Enter the Client Code (or account number). This is the code used to identify the system at the
monitoring station and will usually be issued by the monitoring company.
Enter the connection details as supplied by your monitoring station:
IP Address: The IP address of monitoring station.
IP Port Number: The appropriate port number (in conjunction with IP address) of the monitoring station.
If the monitoring station has a backup path, enter the Secondary IP Address and the Secondary IP
Port Number to be used if the first IP address fails.
Note: Either the IP address, port, or both, should be different. If a backup path is not used, leave these
set at 0.
Select the Reporting Protocol. This will usually be supplied by your monitoring station.
ArmorIP is an ICT proprietary format and the only IP reporting protocol to be UL certified. Wherever
possible, use ArmorIP (TCP) Encrypted for the most robust and secure monitoring format.