Specifications
334 Module 135: Configuring Intruder and Access Integration | Testing the System
Testing the System
Now, we are going to test everything...
Before we do this, disarm all areas.
Testing the Office Area
Arm the office area. The beepers on the Keypad, Office Entry door and Office to Warehouse door should
start beeping
This gives anyone still in the warehouse an audible warning that the Office area is arming
Once armed, the Keypad red LED, and the LED's on the Office Entry door and the Office to Warehouse
door should be flashing
From outside the office, there is now visual indication that the Office area is armed.
Badge Card 6 (our warehouse supervisor) at the Office to Warehouse exit reader (this is the reader that
would be on the warehouse side of the door)
You should be denied access as the Office Area is armed
Badge Card 6 at the Office to Warehouse entry reader (this is the reader that would be on the office side of
the door)
Access is granted. If our warehouse supervisor happened to be trapped in the office when it was armed,
she can still get out. Notice that the Office area stays armed.
Badge Card 3 (our office worker) at the Warehouse to Office reader
Access is granted and the area is disarmed. The Office Entry door also unlocks.
Badge Card 6 (our warehouse supervisor) at the Warehouse to Office reader
This time it is granted. There are now office staff present so access is allowed.