Specifications

Level One: Protege GX Installer Study Guide | August 2013 331
Warehouse Area Indication
Because we want to be able to arm the warehouse from the Multiprox reader, we are also going to have to set
up a schedule to change the door type when armed. While we are at it, we should set up some indication using
reader LED's and beepers.
1. Create a new output group called Warehouse Area Arming
Add outputs RD2 Beeper R1 and RD2 Beeper R2
2. Create another output group called Warehouse Area Armed
Add outputs RD2 Green R1 and RD2 Green R2
3. Assign the new groups to the Warehouse area:
Navigate to Programming | Areas and
select the Warehouse area
Select the Outputs tab
Set the Exit Delay Output Group to
Warehouse Area Arming
Set the Armed Output Group to
Warehouse Area Armed
4. Save your changes