Specifications

Level One: Protege GX Installer Study Guide | August 2013 325
Let's try that test again:
Disarm the Office Area
Set the Controller time to 4:59pm - at 5:00pm, the door locks
Arm the Office area by double badging at the Office Entry reader - the building is locked and secure
Set the Controller time to 8:59am
At 9:00am, the Office Hours schedule goes valid but this time the door stays locked
Badge Card 2 and enter the PIN 9998
The door is unlocked and the Office area disarmed
Note the door stays unlocked
Double badge Card 2 at the Office Entry reader
The Area arms and the door locks
Set the Controller time to 8:58am
Badge Card 2 and enter the PIN 9998
Brett is granted access and the area is disarmed, but the door locks again
At 9:00am the door unlocks
Door Unlocking Integration Summary
1. We've assigned the Office Hours schedule to the Office Entry door as the Operating Schedule
This means that the door will normally unlock when the Office Hours Schedule is valid
2. We assigned the Office Area to the Office Entry door as the Area Inside Door
3. We've enabled the Door Lock Follows Inside Area option
This means that the door will normally unlock when the Office area is disarmed
4. We've enabled the Area Disarmed AND Schedule Valid Unlock Door option
This ties the two together to ensure that the door only unlocks when both the Office Hours schedule is valid and
the Office area is disarmed
Output Groups
Now that we have integrated the access control and intruder functions, it would be good to have some
feedback at the reader as well as at the keypad. This can be achieved using Output Groups.