Specifications

Level One: Protege GX Installer Study Guide | August 2013 321
Configure the Managers Office Outputs
We don't have a keypad to show the status of the managers office, but we do have a reader, so let's set some
outputs for the Managers area:
Navigate to Programming | Areas
Select the Managers Office area and go to the Outputs tab
Set the Exit Delay Output to RD1 Beeper R2
Set Pulse Times of 1 and 9
Set the Armed Output to RD1 Green R2
Set the Pulse Times to 5 and 5
Save your changes
The outputs we have used are the second reader port (R2) on reader expander 1 (RD1)
Wait a few seconds, then try double badge arming at the Managers Office reader. The reader should now beep
during exit delay, then flash the LED while armed.
Configure the Office Entry Door
Badge Card 2 at the Office Entry door twice. Because the door is set for Card and PIN mode, we would have to
badge our card and enter our PIN twice to get the Arm on 2 Reads function to work
A better approach is to set the door mode to Card and PIN if the alarm is armed, and to Card Only if the alarm
is disarmed. To achieve this, we are going to need to create a new schedule that is valid when the Office area is
set, then change the door mode when the schedule is invalid...