Specifications

Level One: Protege GX Installer Study Guide | August 2013 291
Door Monitoring
1. Open the Office Entry Dr (Door) TXS CP1:1 input (using the switch you wired earlier)
You should see a Door Forced Open event, and see the status update on the Technician status page
2. Close the Office Entry Dr (Door) TXS CP1:1 input
3. Badge the Installer card
4. Open the Office Entry Dr (Door) TXS CP1:1 input (to simulate the door opening)
Leave the input open this time and observe what happens:
1. The door opens
2. After 30 seconds an alert is generated
3. After 45 seconds a DOTL (Door Open too Long) alarm is generated
Managers Door
The Office Entry door is now mostly configured according to our system design.
1. Badge your card at the Managers Office reader
2. Open the Managers Dr (Door) TXS CP1:5 input
3. Close the Managers Dr (Door) TXS CP1:5 input
4. Open the Managers Dr (REX) TXS CP1:6 input
5. Close the Managers Dr (REX) TXS CP1:6 input
You should find that the Managers Office door functions correctly, and needs no further configuration.
Configuring Doors
As you can see, basic configuration is completed by the Add Controller Wizard. All that is required now is
configuring any additional options required. We'll come back to this later.
Next, we'll take a look at controlling access with Access Levels and Groups.