Level One: Protege GX Installer Study Guide | August 2013 289
LEDs
1. From the Technician status page, right click the RD1 Green R1 output
2. Set a time of 5 seconds
3. Select Activate Timed
Reader LED's can also be controlled by Protege GX
Reader Single LED Mode
ICT Readers can be configured to operate in either single or dual LED mode. In single LED mode the green
LED control wire (orange) is not connected to the Reader Expander. The blue LED control wire (brown) is
connected to the L1 output of the Reader Expander.
Blue control line grounded
The reader LED strip is GREEN
Blue control line not grounded
The reader LED strip is BLUE
ICT Readers are now shipped with single LED mode set