Specifications

286 Module 134: Basic Access Control | Programming Doors
Door Processing
Door Sense
Badge your card at the reader, then open the Office Entry Dr (Door) TXS CP1:1 input (using the switch you
wired earlier) for a second or two
This time you will see Door Opened and Closed events. Inputs 1 and 5 are configured by default as the Door
Sense (Reed switch) inputs for the doors associated with a Reader Expander
Door Processing occurs independently of any areas the inputs may be associated with as alarm inputs
REX
1. Open the Office Entry Dr (REX) TXS CP1:2 input
Note that the LED input on the Controller changes to red and the status changes to open, but the lock
output does not change state
2. Close the Office Entry Dr (REX) TXS CP1:2 input
You will see an Unlocked Request To Exit event, followed by the lock output cycling for 5 seconds:
REX inputs are inverted by default. This is because many push buttons only have NO (normally open) contacts
which close when the button is pressed. Inputs 2 and 6 are configured by default as the REX (Request to Exit)
inputs for the doors associated with a Reader Expander.
Bond Sense and REN
Inputs 3 and 7 are configured as lock Bond Sense inputs for the doors associated with a Reader Expander
By default, Bond Sense processing is not enabled
Inputs 4 and 8 are configured as REN (Request to Enter) inputs for the doors associated with a Reader
Expander
By default, REN processing is not enabled
Bond Sense and REN processing must be enabled if required