Specifications
284 Module 134: Basic Access Control | Programming Doors
Programming Doors
Navigate to Programming | Doors. You'll see that there are four doors already programmed:
DR 1
DR 2
DR 3
DR 4
This is because the Add Controller Wizard added the doors automatically.
Naming Doors
Using our naming conventions, name the four doors as follows:
DR1 = Office Entry TXS
DR2 = Managers Office TXS
DR3 = Warehouse Roller TXS
DR4 = Office to Warehouse TXS
We have chosen to put the Office Entry and Managers Office on the controller so that if there is a failure of the
RS-485 or of the Reader Expander, we will still be able to gain access to the control equipment (located in the
Managers Office)
Door Testing
Wire a MultiProx reader into Port 1 of the Controller and a NanoProx or Vario reader into Port 2 of the Controller
Shield is frame
grounded at
one point
Shielded Cable
RED
BLACK
GREEN
WHITE
ORANGE
BROWN
BLUE
YELLOW
SHIELD
N/R
N/R
Shield not
connected
V+
V-Z4 V- Z3 Z2 V- Z1BZ L1 D1 DO