Specifications
278 Module 133: Basic Intruder Detection | Programming Inputs
Testing Areas
1. Navigate to the Technician status page
2. Right click the Office area and select Arm
3. Click Close
4. Right click the Warehouse area and select Arm
5. Click Close
6. Right click the Managers Office area and select Arm
7. Click Close
All areas should go through the 10 second exit delay then change to armed.
Testing the Office Area
1. Open the Office (PIR) TXS CP1:4 input
This has been programmed as a Delay input type so should trigger the entry delay.
In the All Events panel you should see the event for the input opening, followed by the Keypad Beeper being
turned on by the Entry function of the Office area.
2. Once the entry delay has timed out, you should see the following:
The keypad beeper is turned off by the entry function
A report is generated (this will send a zone alarm signal to offsite monitoring once configured)
The area alarm is activated
The siren/bell function is activated
The Bell 0 output is turned on by the bell function
3. Leave the system in alarm for now.
After the Alarm 1 Time (1 minute as programmed in the area configuration) has expired, the siren/bell
function will deactivate and the Bell 0 output will be turned off.