Level One: Protege GX Installer Study Guide | August 2013 271
Programming Inputs
1. Navigate to Programming | Inputs
2. Select Input CP1:1 from the Record List
3. Using our naming convention, set the Name to Office Entry Dr (Door) TXS CP1:1
We'll leave the rest of the settings on the General tab as they are:
The Module Address identifies where the device physically connects to the system and allows us to
shift inputs around at a later date if we need to.
The Reporting ID (if defined) will override the report map for Contact ID and offsite monitoring. If left at
0, it will follow the default report map. Only change this value if you want to give the input a specific
number.
The Alarm Input Speed determines how long an input must be open for before an alarm event will be
generated.
The Restore Input Speed determines how long an input must be closed for before a restore event will
be generated.
4. Select the Areas and Input Types tab
Set the Area to the Office TXS area
Set the Input Type to Delay
Inputs can be assigned to as many as four areas and they can perform a different function in each area
independently of the other area's status. For now, we'll just use the first area.