Specifications
222 Module 131: Hardware Programming | Troubleshooting Hardware
Confirm that the server is listening on the correct port. The default event server port is 22000.
This shows that the event server is accepting events on port 22000
Confirm that the Event Server port is correctly set at the Controller
For the DIN Controller this is done via the web interface, but for the PCB Controller this is done via Telnet
If the Event Server diagnostic window shows messages about an unknown serial number, then events are
being received from a Controller with the serial number listed
This also means that the event server is accepting incoming events