Specifications
140 Module 130: Protege GX Hardware Setup | PCB Controller Setup
Setting the Event Server IP
Once the Controller IP address is set, the Event Server IP address must be set to tell the Controller which IP
address to use to send messages to the Event Server.
1. Telnet back into your controller using your new IP address
2. Type D and press [Enter]
3. Type 1 to select the first address and press [Enter]. Type in the IP address of your GX Server and press
[Enter]
In most cases, you will only need to set the first IP address. The other two are used only when there are
multiple paths to your server. Setup of multiple paths is not covered in this training module.
4. Save the changes by typing J and pressing [Enter].
5. You must restart the Controller to apply the changes. Type K and press [Enter], type restart when
prompted, then press [Enter] again. Alternatively, you can restart by cycling power to the Controller.
Defaulting the Controller
It is also good practice to default your Controller when you first install it. This clears out any configuration data,
but leaves all IP configuration intact.
1. To default a Controller, turn DIP switch 4 on, then cycle power to the
Controller.
2. Once the Controller is running (the fault light is off and status light is
flashing once per second), turn DIP switch 4 off again.
Your PCB Controller is now ready to connect to the Protege GX Server.