Specifications
130 Module 127: Protege DIN Rail Hardware Configuration | Review Questions
Where does the shield of the cable connected to a reader get connected?
Frame grounded at one point. Connected to the reader shield.
Wired to V- at the Reader Expander. Connected to the reader shield.
Card reader cable is not shielded.
Frame grounded at one point. Not connected to the reader shield.
Is the wiring method shown in this diagram acceptable?
Assume the power supplies indicated in the diagram shown are DIN Rail PSU's. Is this an acceptable wiring
method? If so, what is the maximum recommended average current that the Controller could draw?
Module #3 Module #1 PRT-CTRL-DIN
NAN+ N- NB
NAN+ N- NB NAN+ N- NB
Module #2
NAN+ N- NB
Power Supply #3 Power Supply #2 Power Supply #1
This is an unacceptable wiring method
Acceptable, 3 Amps
Acceptable, 9 Amps
Acceptable, 4 Amps
What does a constant red fault indicator mean?
The Module is in identification mode
Module communications activity
The module is in error state. The status light will flash an error code.
The module is in boot mode awaiting firmware
What does a continuous fast green flash of the status indicator mean?
The Module is in identification mode
There is Module communications activity
The Module is online
The Module is attempting to register with a Controller