Specifications
126 Module 127: Protege DIN Rail Hardware Configuration | LED Indicators
Battery Indicator
The Battery indicator will show the status of the backup battery.
State Description
Continuous flash (red) Backup battery is disconnected
Constantly on (red) Backup battery failed its dynamic battery test
Constantly on (green) Last backup battery dynamic test successful
Temp Indicator
The Temp indicator will show the status of the unit's core temperature.
State Description
Constantly on (red) Core temperature exceeded. Over Temp Shutdown Activated
Continuous flash (red) Core temperature within 10˚C of Over Temp Shutdown
Constantly on (green) Core temperature OK
Core Temperature on Output Load Operation
In addition to the comprehensive front panel diagnostic indicators, the following table illustrates how the core
temperature of the Power Supply will influence the operation of the V1 and V2 Outputs.
Core Temperature
Output Load Operation Status < 70˚C 70˚C ~ 80˚C > 80˚C
Outputs Enabled (Mains Power)
Outputs Supplied by Battery
Output Over-Current Failure Trouble Input
Activated
Over-Current Output Shutdown Activated