Specifications
116 Module 127: Protege DIN Rail Hardware Configuration | DIN Rail Hardware Setup
Lock Connection
The DIN Rail Controller provides a connection for an electric strike lock with full monitoring of the lock circuit for
tamper and over current/fuse blown conditions. The door lock monitoring can be disabled if it is not required.
+
-
1N4007 Diode
12VDC Electric
Locking Device
B+
B- COM NO COM NO
The lock output is shared with the bell/siren function. You can select another output for the lock control if the
bell/siren function is required. To use the lock outputs in conjunction with the onboard reader module, the Lock
output for the door associated with the reader port must be configured to be the desired lock output on the
controller. This is not configured by default.
When using a door with an Entry and Exit Reader, the lock output should be connected to the Bell (CP001:01),
and the swap lock option for the second reader input should be enabled to allow the reader LEDs to display the
correct status.
Note: The Bell output current must not exceed 1.1A or electronic shutdown will be engaged.
The DIN Rail Controller and RDM2 provide 2 lock output relays that can be used to switch electric locks
+
-
1N4007 Diode
12VDC Electric
Locking Device
+
-
Power Supply for
Locking Devices
Max 30VDC
V+
V- NO C NC NO C NC
When using a door with an entry and exit reader, the LOCK output should be connected to LOCK 1, and
enable the swap lock option for the second reader input to allow the reader LED's to display the correct
status
The 1N4007 diode is supplied with the product and must be installed at the electric strike terminals