Specifications
PRT-WX-DIN Using Protege WX Installation and Programming Manual | June 2013
89
Smoke Reset Output/Output Group: The output (or output group) that is programmed as the keypad
smoke detector reset output will be activated when a user presses the CLEAR + ENTER keys together.
Time User Is Logged In (Seconds): When the user does not perform any action on the keypad for the
programmed time, the keypad will automatically log the user out. Programming the option 'Never Logout'
should be avoided unless for training or demonstration purposes.
Keypads | Options 1
Display Options
Display Custom Message (lines 1 and 2): When enabled, the keypad will display the text programmed in
the Controller settings.
Display Primary Area Status: When enabled, the keypad will display the status of the primary area that is
assigned to the keypad.
Display Scrollable Area Group: When enabled, the keypad will display the status of the area's that are
assigned in the area group.
Display Trouble Message: When enabled, the keypad will display the trouble input(s) when a failure has
occurred.
Display Bypass Message: When enabled, the keypad will display the message input(s) bypassed when an
input has been bypassed in the system or primary area if the Display Primary Area Messages Only option is
also enabled.
Display Alarm Message: When enabled, the keypad will display the message alarm(s) in memory.
Display Primary Area Messages Only: When enabled in conjunction with the Display Alarm Message
option, the keypad will only display the bypassed input status and alarm memory for the primary area of the
keypad. Setting this option means that only the primary area's alarms are shown, in which case, the alarm
message is cleared only if the primary area's memory is acknowledged. If this option is not enabled, then
any area that has an alarm stored in memory is shown and all the area's memory must be acknowledged
before this message is cleared.