Specifications
82 PRT-WX-DIN Using Protege WX Installation and Programming Manual | June 2013
SIA Over IP: SIA Over IP communicates a SIA Level 2 message using the SIA DC09 specification
format to any receiver that supports the SIA DC09 specification. SIA DC09 Specification is currently not
released as a formal specification and is subject to change.
CID Over IP: CID Over IP communicates a Contact ID message using the SIA DC09 specification
format to any receiver that supports the SIA DC09 specification. SIA DC09 Specification is currently not
released as a formal specification and is subject to change.
AlarmNZ IP: AlarmNZ IP is the IP Communication format used by Alarm New Zealand Limited. By
default the AlarmNZ IP service will use the Contact ID reporting format. Information is sent using a login
and password and then event information in a ASCII comma separated data format.
Patriot LS30: Patriot LS30 Protocol is the IP Communication format used by Patriot Systems central
station automation application. By default the Patriot LS30 service will use a form of Contact ID
reporting. Information is sent using a proprietary format and to obtain details the user should contact
Patriot Systems directly.
Back Up Service: A back up service can be programmed to allow the IP reporting functions to be backed
up by a telephone dialer or similar. Using a back up service can be beneficial to allow link failures and
internet access to be reported over an alternate connection.
CID Map Settings: The CID map settings for the service to use.
Area Group: An area group will define which areas this service will process when a reportable event is
generated. An area group of None (default) will result in all areas being sent with the service.
Number of Port Open Attempts: The number of times the service should try and attempt to open the
communications port.
Poll Time: The polling time is set to schedule periodic connections with the server. The polling messages
sent to the receiver will depend on the format. Some formats require that the polling time be set at both the
controller and receivers, in this case ensure that this setting matches the setting provided by the central
monitoring station company.
Encryption Level: The level of encryption for the service.
Encryption Key: The encryption key for the service.
Report Fail Output: The output to activate when the service's communications fail.
Report Fail Output Group: The output group to activate when the service's communications fail.
Time Before Switching to Backup: If a back up service has been programmed, this field defines the length
of time (in seconds) before the service will switch over to backup if it cannot establish a connection through
the specified IP channels. If no backup service is specified, then this field is ignored.
Report IP | Options